Electrical Conductor Voltage Drop & Wire Sizing Calculator
Free engineering voltage drop calculator. Calculate voltage drop percentage, required wire size (AWG & mm²), and maximum cable distance for DC, Single-Phase, and 3-Phase AC circuits with NEC Chapter 9 Table 8/9 compliance.
All formulas and computation matrices for this calculator execute directly in your browser with zero latency. Enter your parameters to see instant results.
Who Uses This Calculation & Why Accuracy Matters
Licensed master electricians, electrical engineers, solar PV installers, and commercial contractors use this calculator to size copper and aluminum branch circuits and feeders to ensure voltage drop remains under the 3% branch / 5% total circuit limits mandated by National Electrical Code (NEC) Informational Note 210.19(A) and 215.2(A)(1).
A homeowner installing a 100-amp 240V subpanel in a detached workshop located 150 feet from the main residential distribution panel.
An electrical contractor routing a 70-amp, 480V three-phase feeder over 350 feet of metallic conduit to a rooftop refrigeration compressor.
A solar technician wiring an 8.5-amp, 400V DC string from ground-mounted solar panels to an inverter 200 feet away.
NEC Conductor Resistance & Ampacity Benchmarks (75°C Copper / Aluminum)
Standard conductor direct-current (DC) and alternating-current (AC) resistance per 1,000 feet in steel conduit from NEC Chapter 9, Table 8 and Table 9.
| Conductor Gauge (AWG / kcmil) | Material | Max 75°C Ampacity (THHN) | DC Ohms / 1,000 ft (75°C) | Max 3% Distance at 80% Load (120V) |
|---|---|---|---|---|
| 14 AWG | Bare Copper | 15 Amps | 3.07 Ω | 41 Feet (12A load) |
| 12 AWG | Bare Copper | 20 Amps | 1.93 Ω | 49 Feet (16A load) |
| 10 AWG | Bare Copper | 30 Amps | 1.21 Ω | 52 Feet (24A load) |
| 8 AWG | Bare Copper | 50 Amps | 0.764 Ω | 49 Feet (40A load) |
| 6 AWG | Bare Copper | 65 Amps | 0.491 Ω | 59 Feet (52A load) |
| 4 AWG | Bare Copper | 85 Amps | 0.308 Ω | 72 Feet (68A load) |
| 2 AWG | Bare Copper | 115 Amps | 0.194 Ω | 84 Feet (92A load) |
| 1/0 AWG | Aluminum | 120 Amps | 0.211 Ω | 74 Feet (96A load) |
| 4/0 AWG | Aluminum | 180 Amps | 0.105 Ω | 100 Feet (144A load) |
* Values based on NEC Chapter 9 Table 8 (Conductor Properties) and Table 310.16. Continuous loads require 125% overcurrent device sizing.
NEC Conductor Ohm's Law Voltage Drop Formulas
For single-phase alternating current or direct current circuits, voltage drop is computed across the two-way conductor run (there and back). For balanced three-phase circuits, the factor √3 (≈1.732) replaces the two-way multiplier of 2.
12.9 ohms-cmil/ft for copper; 21.2 ohms-cmil/ft for aluminum at 75°C.
Circuit current in amperes (A).
Length of conductor from power source to load in feet.
Cross-sectional area of conductor in circular mils (NEC Chapter 9 Table 8).
Source RMS voltage (e.g., 120V, 240V, 208V, 480V).
Step-by-Step Worked Examples with Real Numbers
Single-Phase 120V Outdoor Receptacle Run (100 Feet, 15A Load, 12 AWG Copper)
Three-Phase 480V Commercial Feeder (250 Feet, 60A Load, 2 AWG Copper)
Assumptions, Edge Cases & Common Calculation Mistakes
ℹ Underlying Algorithm Assumptions
- Assumes conductor operating temperature of 75°C under continuous rated load (resistivity constant K=12.9 for copper, 21.2 for aluminum).
- Assumes unity power factor (cos θ = 1.0) unless specified; lagging power factors in inductive loads require AC impedance triangle calculations.
- One-way distance is measured from the breaker terminal to the furthest utilization point along the physical raceway or cable trajectory.
⚠ 3 Common Mistakes to Avoid
- Doubling the one-way distance in the formula when the formula already incorporates the "2 ×" factor for the return conductor path.
- Failing to adjust wire size when running high-amperage continuous loads in conduit through hot attics, violating ambient temperature correction factors (NEC Table 310.15(B)(1)).
- Using nominal wire diameter instead of circular mils (CM = diameter in inches × 1,000 squared).
Frequently Asked Questions
What is the maximum allowable voltage drop under the National Electrical Code (NEC)?
The NEC recommends in Informational Note 210.19(A) and 215.2(A)(1) that voltage drop should not exceed 3% on branch circuits or feeders, and total combined drop from the service entrance to the furthest outlet should not exceed 5% to ensure reasonable operational efficiency.
Why does excessive voltage drop damage electrical equipment?
When voltage drops below nominal rating, motors and compressors draw higher current to produce the same mechanical horsepower (P = V × I). This increased amperage causes severe overheating of motor windings, nuisance breaker trips, and premature dielectric breakdown.
How does conductor temperature affect voltage drop?
Electrical resistance increases as conductor temperature rises. Copper resistance increases approximately 0.393% per degree Celsius above 20°C. For this reason, NEC calculations utilize 75°C conductor properties rather than room temperature properties.
When should I choose aluminum over copper conductors?
Aluminum conductors are substantially lighter and more cost-effective for large feeders (such as 100A to 400A service entrance runs and subpanels). However, aluminum requires roughly two AWG sizes larger than copper to carry equivalent current and necessitates torque-verified dual-rated (AL9CU) mechanical lugs with anti-oxidant paste.
What is a circular mil and how is it related to wire gauge?
A circular mil (cmil) is a unit of area equal to the area of a circle with a diameter of 1 mil (0.001 inch). It simplifies electrical wire calculations by eliminating the factor π/4. For example, a 1,000 kcmil conductor has an area of 1,000,000 circular mils.